Journal of Mechanical Engineering and Automation

p-ISSN: 2163-2405    e-ISSN: 2163-2413

2016;  6(5): 128-138

doi:10.5923/j.jmea.20160605.05

 

Transient Heat Transfer and Energy Balance Model for Hydrodynamic Torque Converters while Operating at Extreme Speed Ratio

Darrell Robinette, Jason Blough

Dep’t Mechanical Engineering-Engineering Mechanics, Michigan Technological University, Houghton, MI, USA

Correspondence to: Darrell Robinette, Dep’t Mechanical Engineering-Engineering Mechanics, Michigan Technological University, Houghton, MI, USA.

Email:

Copyright © 2016 Scientific & Academic Publishing. All Rights Reserved.

This work is licensed under the Creative Commons Attribution International License (CC BY).
http://creativecommons.org/licenses/by/4.0/

Abstract

This investigation details the development of a simple transient model to predict the bulk toroidal flow fluid temperature of the automotive torque converter based upon an energy balance and the derivation of an overall convective heat transfer correlation for the entire turbomachine. Data collected on a torque converter specific dynamometer setup is used to derive a Nusselt correlation for overall convective heat transfer from the shell using measured parameters. Dimensional analysis applied to three torque converters of nearly exact geometric similitude was used to show the applicability of the correlation to prediction of the overall external convective heat transfer mechanism. Discussion is focused on operation at low speed ratios for varying lengths of time. This particular condition represents the worst-case scenario for torque converter operating efficiency and heat rejection. It was found that the external heat rejection from the torque converter shell surface is a function of the rotational Reynolds number and proportional to the characteristic dimensionless performance number unit input speed. The model is shown to trend with temperature measurements made at the external shell of the torque converter over a variety of zero speed ratio transient maneuvers. Overall, the first order, linear differential equation model and Nusselt correlation for overall heat transfer are a first step in developing an adequate tool for use in future torque converter designs predicated on scalability of the turbomachines performance quantified through dimensionless numbers.

Keywords: Torque converter, Transient heat transfer, Nusselt correlation, Dimensional analysis

Cite this paper: Darrell Robinette, Jason Blough, Transient Heat Transfer and Energy Balance Model for Hydrodynamic Torque Converters while Operating at Extreme Speed Ratio, Journal of Mechanical Engineering and Automation, Vol. 6 No. 5, 2016, pp. 128-138. doi: 10.5923/j.jmea.20160605.05.

1. Introduction

The torque converter is a particular class of turbomachine used in a wide variety of power transfer applications to couple the prime mover to the gear system of an automatic transmission. Torque converters can be found in on or off highway powertrain applications and is most commonly utilized in automatic transmissions to enhance the initial acceleration performance of the vehicle. It is also a means of improving system durability since the torque converter has superior cooling characteristics and does not experience wear like that of a friction launch clutch. The modern three-element torque converter consists of a closed loop torus containing a mixed flow pump, a mixed flow turbine and an axial flow stator. The device is required to operate over a range of speed ratios from zero to values greater than one. Speed ratio is defined as the rotation of turbine speed divided by pump speed. At zero speed ratio, maximum torque multiplication is achieved, while maximum efficiency occurs at speed ratios between 0.85 and 0.95 depending on the details of the design. As a result, the flow field is three-dimensional within the torus, producing secondary flow structures and the potential for two-phase mixture, e.g. cavitation, depending on the severity of the specific operating condition. A detailed description of the torque converter and previous experimental or numerical studies can be found in [1-3] for example.
Selection of a torque converter design is performed numerically to match the torque and speed characteristics of the prime mover to a particular powertrain application to balance acceleration and efficiency for the range of operation conditions expected. The geometry of the torus and individual elements is developed through iterative CFD and other numerical methods, and then validated through physical hardware testing on a dynamometer to achieve specific performance targets, see [4-8]. To meet physical packaging constraints or to minimize the occurrence of performance inhibiting toroidal flow structures such as stalled or reversed flow and large volume cavitation, further refinement of the torus dimensions, pump and turbine blade angles and stator blade geometry may be undertaken. Additionally, the working conditions of the hydraulic fluid imposed upon the torque converter pressure vessel can be calibrated to suppress cavitation or create sufficient through flow cooling to maintain adequate toroidal flow operating temperatures.
In automotive powertrain applications, the mega trend is towards increasingly power dense prime movers with greater torque availability at lower operating speeds due to turbocharging. Simultaneously, the dimensions of the torque converter torus are being significantly reduced to accommodate increased gear and clutch content of the automatic transmission to achieve 8, 9, 10 or more forward fixed gear ratios. Additionally, more torus space is being allocated for the lockup clutch damper to bypass the hydrodynamic circuit to further reduce fuel consumption once the vehicle has launched, see Figure 1. The combination of these two design trends results in greater demands on the turbomachine, particularly for extended operation at extreme speed ratios and elevated levels of torque transfer. The purpose of this investigation is to develop a first principal based model validated with experimental data that can predict the internal toroidal flow temperature of the torque converter. The method presented is based upon that reported by [9] for powertrain cooling and protection strategy based upon a predicted temperature internal to the torque converter. Predictions of these temperatures can be critical in determining required cooling capacity, establishing operating limitations for component durability, preventing cavitation and preservation of oil quality from excessive thermal cycling.
Figure 1. Cross-sections of typical three element, automotive torque converters showing typical design trend over past 20 years, from left to right, oldest to newest

2. Torque Converter Fundamentals

The principals of torque converter operation and details of flow theory are contained in a number of sources found in the literature, [1, 4-8 and 10-14], for example. A brief discussion is provided here for reference and continuity of the material contained in this paper.

2.1. Performance Characteristics

Torque converter performance is typically defined by dimensionless or semi-dimensionless quantities to match the turbomachine to specific applications are summarized in Equations 1 through 3. The quantities of torque ratio, TR, output (turbine) to input (engine or pump) torques and K-factor, K, input speed to square root of input torque are plotted versus speed ratio, SR, output to input speeds and forms the mainstay of matching torque converter – prime mover, see Figure 2.
Figure 2. Correlation of one-dimensional flow theory model with measured dynamometer data
(1)
(2)
(3)
K-factor is transformed into the dimensionless quantity unit input speed, , with the addition of diameter, D, to the 5/2 power and square root of the density, ρ, of the operating fluid,
(4)
Unit input speed is the inverse, square root of the more common dimensionless number referred to as the torque coefficient. The designation for a given torque converter are normally specified by the diameter of the pump and the K-factor value realized at zero speed ratio, known as stall.

2.2. One-Dimensional Flow Theory

A significant amount detailed research, both analytical and experimental, has been performed on torque converters, [4-8 and 10-14]. The fundamental laws of fluid mechanics and thermodynamics can be applied to create a one-dimensional flow model capable of useful predictions. The principles of conservation of angular momentum and energy for a control volume, CV, encompassing the fluid and bladed surfaces of the turbomachine elements are used to the define the model as given by Equations 5 and 6, though a thorough description is outside of scope for this paper and is readily available in the literature, see [10-14].
(5)
(6)
The key output of the one-dimensional model are torus fluid operating parameters that are not easily measured experimentally, namely the volumetric or mass flow rate of the toroidal flow. Having this information is important in the prediction of heat transfer from the toroidal flow to the external surface of the torque converter shell. This topic will be discussed in detail later in the paper. One-dimensional models for the torque converters tested for this investigation and example data showing correlation with dynamometer data is provided in Figure 2. Excellent correlation of the model is noted at low speed ratios, which are the focus of the discussion. Figure 3 contains toroidal mass flow rate for the stall, zero speed ratio, condition at a range of pump torques and mass flow rate across the speed ratio range at a pump torque of 150 Nm. At stall, mass flow rate is a linear function with pump torque, corresponding to an increasing pressure head, which will be later shown to adversely affect cooling through at elevated pump speeds. Toroidal mass flow rate follows an inverse power law with respect to speed ratio.
Figure 3. Toroidal mass flow rate as a function of pump torque at stall and speed ratio for a fixed pump torque

2.3. Energy Balance

An energy balance for the torque converter operating with or without the lockup clutch applied is shown in Figure 4. Shaft work input from the prime mover at the cover and pump (green) is converted to useful shaft work through the torus fluid and extracted in the turbine and lockup clutch damper (blue) assembly and then transmitted to the automatic transmission via the turbine shaft. The remainder of the energy not converted to useful shaft work is rejected as heat through two principal pathways. Cooling through flow, is supplied to the torque converter from the automatic transmissions high pressure oil supply which enters through the turbine shaft and mixes with the torus flow and exhausts back to the sump via passages between stator and pump shafts. Energy is also dissipated as heat from the torus to the external shell via forced convection from torus to shell, and shell to air, as well as conduction through the shell. The overall heat transfer mechanism from the external surface can be difficult to measure or quantify using traditional methods and will be a focus of discussion in the paper.
Figure 4. Energy balance across a three torque converter with lockup clutch and cooling through flow circuit
Based upon the energy balance in Figure 4, a linear, first order, differential equation can be written for the temperature of the toroidal fluid temperature, , as seen in Equation 7. It should be noted that for this model, it is assumed that torus temperature is equivalent to the exhaust or outlet temperature from the torque converter.
(7)
The individual heat transfer mechanisms of and in additional to conduction through the shell can be combined into an overall heat transfer term, given by,
(8)
The solution of the differential equation of Equation 7 for torus temperature becomes,
(9)
where and are equal to the following,
(10)
and
(11)
Assuming an initial condition for the torus temperature, , to be equal to the cooling through flow inlet temperature, which is assumed to be time invariant. A simplification can be made to Equation (9) if the amount of heat energy rejected through the external surface is assumed a known quantity,
(12)
which results in the following solution for torus temperature with the same initial condition,
(13)
Equation 13 will be the foundation for the remainder of the discussion in this paper for estimating the toroidal flow temperature of the torque converter during transient operation. Detail will be provided in the results section as to the mechanism enabling the simplification through the development of a proportional relationship between overall external surface heat rejection and input power based upon the specific design details of the torque converter.

3. Experimental Setup

A torque converter specific dynamometer test cell, Figure 5, was used to test three torque converters of nearly exact geometric scaling, see Figure 6, at stall. The testing was originally performed to determine the appropriateness of applying the dimensional analysis to developing a prediction tool for incipient cavitation in torque converters using a nearfield acoustical technique, see [8]. The dynamometer data collected during this testing can be further utilized to develop a model to predict torus temperatures during transient, high input power maneuvers when operating at low overall efficiency. The dynamometer was setup for the stall condition, zero output speed, only and all three torque converters were painted flat black to create the same radiation surface emissivity and to enable a more suitable infrared surface temperature measurement. The details of this measurement setup can be seen in Figure 5, along with nearfield microphones to detect cavitation enclosed in a nitrile cover to prevent oil contamination. The torque converters tested were 245, 258 and 300 mm diameters as measured at the pump outside diameter and had a stall unit input speed rating of 140, corresponding to K-factors of 163, 146 and 101, respectively. Figure 7 contains performance data, K-factor and torque ratio as a function of speed ratio, from dynamometer testing for the three torque converters tested in this investigation. The near perfect geometric scaling of all three torque converters results in the value of the dimensionless unit input speed to be equivalent across the range of speed ratios tested as noted in Figure 8.
Figure 5. Torque converter specific dynamometer test cell and test fixture instrumentation
Figure 6. Geometrically scaled torque converters tested with U = 140, from left to right, 300 mm, 258 mm and 245 mm pump diameters
Figure 7. K-factor and torque ratio vs. speed ratio for the three torque converters tested for this investigation
Figure 8. Unit input speed and torque ratio vs. speed ratio for the three torque converters tested for this investigation

4. Results

4.1. Stall Speed Sweeps

A common set of stall speed sweep tests were performed for this investigation, ramping pump speed of the torque converter from 100 r/min to maximum speed ranging between 2500 to 2900 r/min depending on the design being tested. Pump speed was swept at four ramp rates of 40, 100, 200 and 500 r/min/s. These ramp rates were selected to span those realized during vehicle operation. The worst case condition is 40 r/min/s for internal heat build-up in the torus fluid to a ramp rate of 500 r/min/s more typical of operation in a vehicle powertrain. Once the peak pump speed was achieved, pump speed was ramped down to a 100 r/min at a ramp rate of -300 r/min/s. Once pump speed reached 100 r/min, an extended cool down period was allowed for torus fluid temperature to stabilize to that of the oil supply. The stall speed sweep test procedure and measurements of cooling through flow rate and temperatures at the inlet, outlet and surface of the torque converter shell is summarized in Figure 9 for a sweep rate of 40 r/min/s. Figure 10 contains the stall speed sweep temperature data for all sweep rates for the 258 mm torque converter showing only the ramp up in speed portion of the test.
Figure 9. 258 mm torque converter, cooling mass flow rate and operating temperatures during a 40 r/min/s stall speed sweep and subsequent cool down period
Figure 10. 258 mm torque converter surface and outlet temperatures during various stall speed sweep tests
As expected, the rate of temperature rise and absolute value achieved is proportional to the sweep rate, however, cooling flow rate through the torque converter drops equivalently and independently of the sweep rate. The drop in cooling flow rate is a direct result of the pressure head developed in the torus as pump speed increases and rises above the charging pressure, impeding flow. Cooling through flow increases once the charging pressure is higher than the pressure developed in the toroidal flow. Thus, a time lag between the rise in outlet temperature of the fluid exiting the torque converter torus and the peak pump speed during the test can be noted in Figure 9. As sweep rate increases the rise in temperatures decreases sharply as the amount of energy input into the torque converter is reduced significantly. The most severe operating scenario occurs with the slow sweep rates combined extended operation at elevated power input.
The effect of torque converter size on output and shell surface temperatures are found in Figure 11. As the physical size of the torque converter increases, the rate of change of temperatures decreases, though the time required to return to a steady state oil temperature equal to the inlet oil temperature remains roughly constant for all three diameters.
Figure 11. Effect of torque converter size on surface and outlet temperatures at a 40 r/min/s stall speed sweep rate and cooling cycle

4.2. Cooling Flow Heat Transfer

The cooling through flow to the torque converter torus acts as a mixing flow heat exchanger. Cooler automatic transmission oil enters the torus through flow passages in the turbine shaft and mixes with warmer torus fluid, causing displacement of warmer fluid to exit through passages in the stator shaft. This process is roughly depicted in Figure 4 and can be approximated as a heat exchanger with the amount of heat transferred determined from the following,
(14)
It was assumed that the outlet or exhaust temperature from the torque converter was equal to the internal torus temperature. Any heat transfer occurring in the passages within the shafting or test fixture were ignored. The heat rejection from cooling can directly be calculated since the mass flow rate of cooling oil, inlet and exhaust temperatures are measured during the test. Heat rejected during a 40 r/min/s stall speed sweep and following cooling cycle is plotted in Figure 12 along with mass flow rate of cooling for the three diameter torque converters tested. As indicated in Figure 12, heat rejection is minimal during the ramp up in pump speed as an increasing temperature differential between inlet and outlet is offset by a decreasing flow rate of cooling oil. All significant removal of heat from the through flow cooling circuit occurs after the stall event, ranging between 36 and 45 kW. During the stall event, the dominant mode of heat removal is forced convection at the outer shell.
Figure 12. Heat rejection from cooling through flow for 245 mm, 258 mm and 300 mm torque converters during 40 r/min/s stall speed sweep and cool down cycle

4.3. Overall External Heat Transfer Coefficient – Conventional Approach

This section will detail calculations of heat transfer coefficients and rates related to determining the amount of heat rejected through the external surface of the torque converter. The rotational Reynolds number, Equation 15, was used in this investigation to characterize the turbomachines operating flow regime for both internal and external flows. For internal flow, the critical Reynolds number for transition to turbulent flow is 2500 while for external flow the transition point was taken to be 250000.
(15)
4.3.1. Internal Convection
The heat transfer coefficient for forced convection from the torus flow was determined using the Nusselt correlations in Equations 16 and 17 for laminar and turbulent flow, respectively, approximating the individual blade passages within the torque converter elements as rectangular passages.
(16)
(17)
4.3.2. External Convection
External heat transfer coefficients were sought out from multiple sources, namely flow over a flat plate, [15], and rotating disks or cylinders in air, [16,-18]. Both approaches yielded similar heat transfer coefficients for the given geometry and boundary conditions. However, those derived specifically for rotating disks in air were selected due to the closer approximation to the rotating torque converter in the test fixture. The Nusselt correlations utilized are from testing conducted by [17] and are as follows,
(18)
(19)
For the external surface geometry, rotation speeds between 100 and 3000 r/min and the fluid properties of air result in heat transfer coefficients in the range of 0.01 to 0.25 kW/m2-K. These values are an order of magnitude less than those computed for internal heat transfer and will be a limiting factor on overall heat rejection from the external surface. The net result will be prediction of torus fluid temperatures being unrealistically high for the stall speed sweep tests as will be presented next.
4.3.3. Overall Heat Transfer Coefficient
The internal and external heat transfer coefficients found using available Nusselt relationships were combined with the conduction coefficient through the torque converter shell to define an overall heat transfer coefficient as described in many heat transfer textbooks, [19] for example. The limiting factor for the overall heat transfer coefficient becomes the external forced convection with a heat transfer coefficient an order of magnitude less than that of internal convection for the torus to the shell. The result is minimal heat rejection through the external shell to the air, which during a slow stall speed sweep in which power input is relatively high throughout the majority of the stall maneuver will produce extreme torus temperatures. An example prediction of torus flow temperature using Equation 9 and an overall heat transfer coefficient from Equations 16 to 19 for a 258 mm torque converter is shown in Figure 13. Also included in Figure 13 are measured surface and outlet temperatures during the 40 r/min/s stall speed sweep. As expected with the minimal overall heat transfer coefficient for external surface heat rejection, torus temperature is predicted to peak at an unreasonably value of 900°C. It was concluded that the available Nusselt relationships cannot be applied to this particular situation with good confidence and that an alternative Nusselt relationship must be derived.
Figure 13. Torus fluid temperature prediction using available Nusselt relationships and Equation 9 for 258 mm, 140 unit input speed torque converter during 40 r/min/s stall speed sweep and cooling cycle

4.4. Overall External Heat Transfer Coefficient – Derived Nusselt Correlation

A Nusselt correlation unique to this particular heat transfer aspect for torque converter applications is derived to predict the external heat transfer mechanism more appropriately. Similar approaches to predict heat transfer have been defined by [20, 21] as applied to automotive turbochargers and torque converter lockup clutches, respectively. The heat energy rejected through the torque converter external surface can be reduced to the relationship of Equation 20 assuming the heat energy rejected is proportional to the input power by the scaling factor,
(20)
Such an assumption is appropriate given the energy balance of Equation 12, knowing that the balance of input power must be absorbed in the torus fluid to be removed by the cooling through flow or rejected from the external shell surface. As shown earlier, minimal amount of energy is removed by cooling flow during the high power input stall speed sweep, thus a significant amount of the input power is transferred to the torus fluid to be rejected from the external shell surface. Utilizing traditional Nusselt correlations and combining internal and external convection with conduction through the shell into an overall heat transfer coefficient, an insufficient amount of heat rejection was determined to be computed by this method. The result was an unrealistic torus fluid temperatures approaching 900°C for the slowest sweep rates.
Owing to similitude and previous Nusselt correlation work for rotating disks and assemblies by [16, 17 and 18], it is known that a similar Nusselt relationship should result for this particular turbomachine. The scaling factor, should be a function of the torque converter design, size and performance attributes, such as unit input speed and operating fluid properties. For this investigation, it was found that scaling the input power by Equation 21 resulted in a universal Nusselt correlation, see Equation 22, for the three diameter torque converters tested.
(21)
Curve fitting a power function to the data reveals the Nusselt correlation of the formas shown in Figure 14. The rotational Reynolds number for the testing performed extend to a value of 300,000, corresponding to the transition region reported by [17] and thus can be assumed to reside mainly in the laminar region for external forced convection from a rotating assembly in quiescent air. Interestingly, the values of the power law curve for Nusselt verse Reynolds number are similar in form and value to those found by [17] for the transition region for rotating disk heat transfer. The Nusselt correlation in Equation 22 is applied in the prediction of torque converter torus fluid temperature expressed by the first order, linear differential equation expressed by Equation 13. Equation 22 is valid for the stall operating condition only and for torque converters with dimensions scaled from the designs tested in this investigation that yield a stall unit input speed of 140.
Figure 14. Derived Nusselt correlation for overall heat transfer coefficient from torque converters of constant unit input speed and geometric scaling
From a torque converter design standpoint, the scaling factor found in Equation 21 shows that torque converters of increasingly higher unit input speed and K-factor will result in higher heat rejection through the external shell. However, further dynamometer testing of such designs is required to substantiate the observation and establish design guidelines.

4.5. Model Correlation and Torus Fluid Prediction

The derived Nusselt correlation of Equation 22 was used as an input for the solution of the differential equation describing the energy balance of the torque converter, Equations 12 and 13, at stall to predict the torus fluid temperature. The models prediction capability is shown for two examples, the results of which are contained in Figures 15 and 16. In the first example, the 258 mm torque converter is performing a 40 r/min/s stall speed sweep and cool down cycle. The predicted torus temperature leads the surface temperature measurement in very close association, while outlet temperature lags predicted torus temperature as cooling flow drops during high stall speeds then surges once pump speed drops. It can be noted that torus temperature drops rapidly once cooling mass flow rate increases, and sufficient cooling flow mixes with the hot torus fluid, being fully replaced within a period of approximately 15 seconds.
Figure 15. Torus fluid temperature prediction using derived Nusselt relationship and Equation 13 for 258 mm torque converter during a 40 r/min/s stall speed sweep and cool down period overlaid with surface and outlet temperatures
The same general observations are made for the case of the 245 mm torque converter performing a stall speed sweep at 200 r/min/s followed by a subsequent cooling cycle. Predicted torus temperature leads measured surface temperature with good association followed with a lagging outlet temperature during the cooling phase, continuing until convergence after adequate mixing of cooling and torus flows at approximately 80 seconds in Figure 16.
Figure 16. Torus fluid temperature prediction using derived Nusselt relationship and Equation 13 for 245 mm torque converter during a 200 r/min/s stall speed sweep and cool down period overlaid with surface and outlet temperatures
Overall, the linear first order, differential equation describing the torus fluid temperature based on the energy balance of the torque converter combined with the derived Nusselt relationship for overall heat transfer from the external surface provides sufficient capability for adequate prediction of toroidal flow temperatures during transient stall maneuvers. The predicted values show that extended operation at extreme speed ratios can be detrimental to the fluid, breaking down viscosity modifiers and compromising long term durability of internal transmission components as temperatures can reach beyond the typical recommended operating temperature of 120°C for most automatic transmission fluids. Additionally, the predicted torus fluid temperatures during the extended stall operation at high input powers can promote cavitation.

4.6. Future Developments

The transient model presented in this investigation was derived focusing on the stall operating condition, which is an extreme condition, but most severe for thermal loading of the torus fluid. Future testing should focus on the development and validation of the model for transient or steady state speed ration operation between 0 and 1. This is will require potential further development of the derived Nusselt relationship which may take the following functional relationship,
(23)
including the additional terms of speed ratio, SR, and unit input speed, , in the case of different torque converter designs. Expansion of the Nusselt relationship and scaling factor on external heat rejection as a function of input power would increase the predictive capability of the model and methodology presented to future torque converter designs across the entirety of their operating range.

5. Conclusions

A first order, linear differential equation model based upon an energy balance of the torque converter was developed to predict internal torus fluid temperatures at the extreme stall operating condition, zero speed ratio. A Nusselt correlation was derived specific to the overall turbomachine for external heat transfer as it was found that conventional relationships were inadequate in accurate prediction. The heat rejected from the torque converter external surface was found to be proportionally scaled by the two times the square root of the torque converters diameter to the power of 5 and operating fluid density and a semi-dimensionless attribute, K-factor, raised to the power of 1.5. This relationship was shown to collapse the Nusselt relationship to a single function of the rotation Reynolds number for three torque converters of geometric similitude. Prediction of torus temperatures trended with measured temperature data acquired at the shell surface and outlet flow during dynamometer testing. The next steps in this research would be to develop fully the Nusselt relationship to include speed ratios other than stall to enhance its prediction capability for all operating conditions the torque converter experiences during typical powertrain maneuvers in vehicle applications.

Nomenclature

References

[1]  Jandasek, V. J., "Design of Single-Stage, Three Element Torque Converter," SAE Design Practices: Pass. Car Auto. Trans., 3rd Ed., 75-102, 1961.
[2]  Abe, H., Tsuruoka, M., Muto, A., Kato, M. and Fujiwara, H., “Development of Super Flat Torque Converter with Multi Plate Lock-up Clutch,” SAE Technical Report, 2009-01-0141, 2009, doi: 10.4271/2009-01-0141.
[3]  Usui, T., Okaji, T., Muramatsu, T., and Yamashita, Y., "Development of a Compact Ultra-Flat Torque Converter Equipped with a High-Performance Damper," SAE Int. J. Engines 8(3):1374-1378, 2015, doi:10.4271/2015-01-1088.4.
[4]  Bahr, H. M., Flack, R. D., By R. R. and Zhang, J. J., “Laser Velocimeter Measurements in the Stator of a Torque Converter,” SAE J. of Pass. Cars, 99:1625-1634, 1990.
[5]  By, R. R. and Lakshminarayana, B., “Measurement and Analysis of Static Pressure Field in a Torque Converter Turbine," ASME J. of Fluids Eng., 117(3): 473-478, 1995.
[6]  Schweitzer J., Gandham, J., “Computational Fluid Dynamics in Torque Converters: Validation and Application,” International Journal of Rotating Machinery, vol. 9, pp. 411-418, 2003.
[7]  Robinette, D., Grimmer, M., Horgan, J., Kennell, J. et al., "Torque Converter Clutch Optimization: Improving Fuel Economy and Reducing Noise and Vibration," SAE Int. J. Engines 4(1):94-105, 2011, doi: 10.4271/2011-01-0146.
[8]  ] Robinette, D. L., Schweitzer, J. M., Maddock, D. G., Anderson, C. L., Blough, J. R. and Johnson, M. A., “Predicting the Onset of Cavitation in Automotive Torque Converters – Part II: A Generalized Model,” Int. J. of Rotating Machinery., Vol. 2008, 312753, 2008.
[9]  Williams, B., Kelly, J., Varda, D. and Shockley, S., “Transmission and Torque Converter Cooling Control,” Patent, 6,959,239, filed February 24, 2004, and issued October 25, 2005.
[10]  Ishihara, T. and Emori, R., "Torque Converter as a Vibration Damper and Its Transient Characteristics," SAE Technical Paper 660368, 1966, doi:10.4271/660368.
[11]  Tsangarides, M. and Tobler, W., "Dynamic Behavior of a Torque Converter with Centrifugal Bypass Clutch," SAE Technical Paper 850461, 1985, doi:10.4271/850461.
[12]  Xia, H., and Oh, P., “A Dynamic Model for Automotive Torque Converters,” Int. J. of Vehicle Design, 21(4/5): 344-354, 1999.
[13]  Hrovat, D., and Tobler, E., “Bond Graph Modeling and Computer Simulation of Automotive Torque Converters,” J. of Franklin Institute, 319(1/2):93-114, 1985.
[14]  Fujita, K. and Inukai, S., "Transient Characteristics of Torque Converter-Its Effect on Acceleration Performance of Auto-Trans. Equipped Vehicles," SAE Technical Paper 900554, 1990, doi:10.4271/900554.
[15]  Incorpera, F., et. al., “Fundamentals of Heat and Mass Transfer,” 7th Edition, Wiley, New Jersey, ISBN 978-0470501979, 2011.
[16]  Becker, K., “Measurements of Convective Heat Transfer from a Horizontal Cylinder Rotating in a Tank of Water,” International Journal of Heat Transfer, Vol. 6, pp. 1053-1062, 1963.
[17]  Cardone, G., Astarita, T., and G. M. Carlomagno, “Heat Transfer Measurements on a Rotating Disk,” Int. J. of Rotating Machinery, vol. 3, no. 1, pp. 1-9, 1997. doi:10.1155/S1023621X97000018.
[18]  Ozerdam, B., “Measurement of Convective Heat Transfer Coefficient for a Horizontal Cylinder in Quiescent Air,” Int. Comm. Heat Mass Transfer, Vol. 27, No. 3, pp. 389-395, 2000.
[19]  Bergman, T., Lavine, A., Incropera, F., “Fundamentals of Heat and Mass Transfer, 7th Edition,” Wiley Global Education, 2011, ISBN 1118137256, 9781118137253.
[20]  Cormerais, Mickaël, Pascal Chesse, and Jean-François Hetet. "Turbocharger Heat Transfer Modeling Under Steady and Transient Conditions." International Journal of Thermodynamics, Vol 12, No. 4, pp. 193-202, 2009.
[21]  Karamavruc, A., Shi, Z., and Gunther, D., "Determination of Empirical Heat Transfer Coefficients via CFD to Predict the Interface Temperature of Continuously Slipping Clutches," SAE Technical Paper 2011-01-0313, 2011, doi:10.4271/2011-01-0313.